Design Heating Conditions
- Hot Water 110/96 deg F @ 130 gpm (20% PG)
- Source Water 45/37 deg @ 190 gpm (40% PG)
Design Cooling Conditions
- Chilled Water 45/56 deg F @ 130 gmp (20% PG)
- Source Water 110/120 deg @ 190 gpm (40% PG)
Shown at right 90 ton self contained heat pump skid:
- 1 ea 90 ton screw compressor (High Head conditions)
- R-134a
- Capable of providing 120 degree Supply Water (20% PG) at 37 degree Source (40% PG)
- Inline Pumps
- Air Seperator and Expansion Tank
- 400 Gallon Thermal Storage Tank
- ETL Listed
- Graphics Control Panel
Shown at right 80 ton self contained heat pump skid:
- 2 ea 40 ton Heat Pumps
- Inline Pumps
- Air Separator and Expansion Tank
- 400 Gallon Thermal Storage Tank
- ETL Listed
- Single Point Connections
Heat Pump Systems
- Custom Size 20 to 600 tons
- Custom Engineered or Prepackaged
- Screw Compressor or Scroll Compressor
- Full Controls
- Graphics based Microprocessor
- Configured with:
- Pumps
- Thermal Storage Tanks
- Air Separator and Expansion Tank
- Engineered:
- FEA analysis
- Flow analysis
- ETL
- Tested
Bosch 80 ton Pump Skid